Menu item

Parameter

Factory setting

WKF

WKF

Duo

4th mixed heating cycle

Activated / Deactivated

Deactivated

-

X

Heating cycle mode

Heating curve

Deactivated

-

X

Heating-curve base point

"15°C - 25°C"

20 °C

-

X

Standard inlet temperature "28°C - 90°C"

35 °C

-

X

Standard outside temp.

"0°C - 20°C"

20 °C

-

X

System separation FBH

Activated / Deactivated

Deactivated

X

X

Setpoint increase

0 - 10 K

5.0 K

X

X

Building time constant

"0 h - 100 h"

10 h

X

X

Standard heating load

"0 kW - 25 kW"

As required

X

X

Cooling function

Activated / Deactivated

Deactivated

X

X

Separate cooling cycle

Activated / Deactivated

Deactivated

X

X

Cooling via unmixed

heating cycle

Activated / Deactivated

Deactivated

X

X

Solar plant

Activated / Deactivated

Deactivated

X

X

Pump type

Asynchronous

Deactivated

X

X

Asynchronous speed

control system

On / Off

Deactivated

X

X

Pump type

EC pump

(high-efficiency pump)

Deactivated

X

X

Solar speed control syst.

Activated / Deactivated

Deactivated

X

X

Solar HM

Deactivated

Deactivated

X

X

Manual medium flow rate

2 l/min - 30 l/min

5.0 l/min

X

X

Medium flow rate probe

0 ml / lmp - 10 ml / lmp

5.7 ml / lmp

X

X

Heat carrier medium

As required

Tyfocor-L

X

X

Solar set temperature

"5°C - 95°C"

85°C

X

X

Acquisition of the

stored energy

Activated / Deactivated

Deactivated

X

X

57