Cooling function

Activate (select with the rotary knob and confirm

with "OK") if the building is to be actively cooled

with the heat pump in summer.

Please ensure that the cycle being used for the

cooling function is designed for this purpose.

Fig. 76: Activating the cooling function

Menu item

Parameter

Factory setting

Cooling

function

Deactivated

Deactivated

Activated

Press "Next".

Separate cooling cycle

Activate (select with the rotary knob and confirm

with "OK") if a separate cycle is installed which is

used solely for the cooling function (e.g. with fan

convectors).

Fig. 77: Activating the separate cooling cycle

Menu item

Parameter

Factory setting

Separate

cooling cycle

Deactivated

Deactivated

Activated

Press "Next".

Cooling via unmixed heating cycle

If active cooling is to take place via the unmixed

heating cycle, this parameter is activated.

Fig. 78: Cooling via unmixed heating cycle

Menu item

Parameter

Factory setting

Cooling via

unmixed

heating

cycle

Deactivated

Deactivated

Activated

Solar plant

Deactivate (turn the rotary knob to the left and con-

firm with "OK") if no solar plant is installed. It can

be activated again at a later date.

Activate (turn the rotary knob to the right and con-

firm with "OK") if a solar plant is installed.

Fig. 79: Deactivate solar plant

Menu item

Parameter

Factory setting

Solar plant

Deactivated

Deactivated

Activated

REMKO Smart WP MANAGER