Fig. 96: Output restriction cooling (reduced)
The output restriction in "reduced" cooling mode
(22:00 - 06:00 hrs) is set to 90% in the factory.
Adjustment must take place depending on the
building.
Fig. 97: Output restr. Hot water (normal)
The output during hot water preparation (HW) in
"normal" operation (06:00 - 22:00 hrs) is fully ena-
bled. Enablement is issued by the factory with just
one compressor (outdoor unit Fig. 99)
Fig. 98: Output restr. Hot water (reduced)
The output restriction of the hot water preparation
(HW) in "reduced" operation (06:00 - 22:00 hrs) is
reduced to 60%. If no hot water preparation should
take place during this time, a corresponding time
program must be stored at time program, hot water
level. The factory setting here is 24 h enabled.
Fig. 99: Compressor restriction (normal)
Restriction of the enabled compressors (outdoor
unit), which are in operation during hot water prep-
aration (time program hot water "normal" opera-
tion, e.g. 06:00 - 22:00 hrs). Factory setting 1 com-
pressor.
Fig. 100: Compressor restriction (reduced)
Restriction of the enabled compressors (outdoor
units), which are enabled during "reduced' opera-
tion.