Fig. 96: Output restriction cooling (reduced)

The output restriction in "reduced" cooling mode

(22:00 - 06:00 hrs) is set to 90% in the factory.

Adjustment must take place depending on the

building.

Fig. 97: Output restr. Hot water (normal)

The output during hot water preparation (HW) in

"normal" operation (06:00 - 22:00 hrs) is fully ena-

bled. Enablement is issued by the factory with just

one compressor (outdoor unit Fig. 99)

Fig. 98: Output restr. Hot water (reduced)

The output restriction of the hot water preparation

(HW) in "reduced" operation (06:00 - 22:00 hrs) is

reduced to 60%. If no hot water preparation should

take place during this time, a corresponding time

program must be stored at time program, hot water

level. The factory setting here is 24 h enabled.

Fig. 99: Compressor restriction (normal)

Restriction of the enabled compressors (outdoor

unit), which are in operation during hot water prep-

aration (time program hot water "normal" opera-

tion, e.g. 06:00 - 22:00 hrs). Factory setting 1 com-

pressor.

Fig. 100: Compressor restriction (reduced)

Restriction of the enabled compressors (outdoor

units), which are enabled during "reduced' opera-

tion.

REMKO Smart WP MANAGER

78