Gasboy 1000 Series FMS Startup Manual User Manual
Page 40

Communications Tests
03/07/03
9-3
Testing the Tank Monitor
a. Determine the device (direct connect or modem) from which the tank monitor will be
contacted and follow steps a through d of Testing the Direct Connect Device or Testing
the Modem.
b.
Type
TM. The system prints TANK MONITOR LINK?
c.
Type
Y and press RETURN. The system should respond with the > symbol indicating
connection to the tank monitor.
d. Type any valid tank monitor command and the tank monitor should return the appropriate
response.
e. Press CTRL E. The system should respond with an asterisk (
*
) indicating it has
terminated communications with the tank monitor and has resumed communications with
the Series 1000.
f.
Type
EX. The system prints EXIT.
Testing the Fuel Point Reader
a. Connect a terminal to port 1 (direct printout port).
b. Turn FPR power switch on. The terminal should respond FPR communications
established @date time.
c. Turn FPR power switch off. The terminal should respond FPR communications lost
@date time.