AUXILIARY COMMUNICATIONS PORT PCB ASSEMBLY


When the system is equipped with a receipt printer, tank monitoring system, or Fuel Point Reader,
an additional board is required. The Auxiliary Communications Port PCB assembly (Figure 5-4) is
attached to the Series 1000 MPU Board via the expansion port (shown in Figure 5-2).

Figure 5-4. Auxiliary Communications Port Board



Veeder-Root TLS-250 Tank Monitor Switch Settings

When the Series 1000 is connected to a Veeder Root TLS-250 tank level sensor, set the baud
rate jumper for 300 or 1200 baud. Setting the baud rate at 9600 is not recommended and may
result in a loss of data received from the TLS-250.

The Option PCB, located inside the right hinged cover of the TLS-250 contains a rotary switch
which must also be set. The switch is located at the lefthand center of the PCB and shows a
numbered switch position. This switch should be set to 4 (1200 baud) or 6 (300 baud) to match
the setting used in the Series 1000.