GASBOY Series 1000

5-4

03/07/03

15. If your Series 1000 system has a Tripp Lite battery backup installed, remove the jumper or

wire wrap on jumper patch JP8. This jumper must be removed to allow normal operation of
the data terminal in a power fail condition. The JP8 jumper patch is located next to the
diagnostic and reset switches on the right edge of the MPU PCB.


16. Pulse Rate - The pulse rate switch is mounted on the back side of the microprocessor PCB

and can be accessed through a hole in the sheet metal on which the microprocessor PCB is
mounted. Move this switch towards the rear of the unit to enable the pulse rate to be set
during the configuration of the system. NOTE: When the pulse rate switch is set to enabled,
no transactions can occur at the system and the message REMOTE CONFIGURATION
appears on the display. Be sure to set it to disabled when pulse rate setting is complete.


17. Locate the pump control PCB(s) mounted to the rear door of the Series 1000 System (see

Figure 5-3 for Steps 18-28).


18. Remove the flat ribbon cable connector from each of the pump control PCB’s. (Ribbon cable

is not shown in Figure 5-3. It attaches at the top right of the board).


19. Remove the two Phillips head screws which attach the pump control PCB bracket to the

pump control card cage.


20. Note the orientation of the three black connectors on the opposite side of the pump control

PCB for hoses 1 and 2. Remove these cables from the rear of the PCB. Slide the pump
control PCB out of the card cage.


21. Pulse Configuration - Set the pulser configuration jumpers for hose 1 according to the type of

pulser used. Set the pulser configuration jumpers for hose 2 according to the type of pulser
used.


22. Pulse Rate (Debounce) - Set the pulse rate jumper according to the highest resolution pulser

that is used on either hose (e.g., if hose 1 has a 10:1 pulser and hose 2 has a 100:1 pulser,
set the jumper for 100:1).


23. Address - Verify that the pump control PCB is set for the proper address. This is jumpered at

the factory and should be correct.


24. Slide the pump control PCB into the pump control card cage and screw it into place. Re-

attach the three cables to the rear of the PCB. (NOTE: These cables are keyed to prevent
them from being installed upside down
). The cable for hose 1 attaches to side 1 (J1) and the
cable for hose 2 attaches to side 2 (J2). The orientation of the sides is shown in Figure 5-3.


25. If the hardware for hoses 3 and 4 is installed, repeat Steps 19-24 substituting hose 3 for hose

1 and hose 4 for hose 2. If not available, skip to Step 28.


26. If the hardware for hoses 5 and 6 is installed, repeat Steps 19-24 substituting hose 5 for hose

1 and hose 6 for hose 2. If not available, skip to Step 28.


27. If the hardware for hoses 7 and 8 is installed, repeat Steps 19-24 substituting hose 7 for hose

1 and hose 8 for hose 2. If not available, skip to Step 28.


28. Reconnect the ribbon cable to the pump control PCB(s).