Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate the
voltage drop from the following formula:

2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP

Table 4-2: Suggested Output Wiring Sizes*

Load Current

Wire Gauge (US)

Circular Mils

(kcmils)

Metric (mm2)

65 AMPS

8 AWG

16.5

8.37

130 AMPS

4 AWG

41.7

21.2

260 AMPS

2/0 AWG

133.0

67.4

400 AMPS

4/0 AWG

212.0

107.0

* Data shown for use of high temperature (100° C) rated stranded copper wire, unbundled and not installed
in conduit. Adjust wire gauge for Aluminum wire type.

Note:

Use high temperature rated wire. Always consult the National Electrical Code and local code
regulations for proper rating and size of wire cabling prior to installation.