7. Move the DMM leads to the C module terminals 6 and 7 in the auxiliary cabinet. Press the OUTPUT

ON/OFF key again to enable the output. Verify the phase C module output is within 50mVolts of the
C module in the master cabinet. If it is not, adjust the pot behind the hole in the upper left corner of
the module so the C output matches the C master output within 50mVolts. Repeat for the C’ module.
Press the OUTPUT ON/OFF key to disable the output.

8. Power down system and replace the wires to terminals 6 and 7 on the auxiliary power modules.