AMETEK Programmable Power

BPS Series User Manual M440077-01 Rev A

31

be a function of the voltage range and phase mode on some BPS models. If the BPS has more than one
output voltage range, size the wires for the lowest available voltage range as the currents will be highest
in that range.

Cable lengths must not exceed twenty-five (25) feet. For lengths greater than 25 feet, calculate the
voltage drop from the following formula:

2 X DISTANCE X CABLE RESISTANCE PER FT. X CURRENT = VOLT DROP

Table 3-2: Suggested Output Wiring Sizes *

Load Current

Wire Gauge (US)

Circular Mils

(kcmils)

Metric (mm2)

65 AMPS

6 AWG

26.24

13.3

130 AMPS

4 AWG

41.74

21.1

260 AMPS

1/0 AWG

105.6

53.5

400 AMPS

2/0 AWG

133.1

67.4

Note:

Use high temperature rated wire. Always consult the National Electrical Code and local code
regulations for proper rating and size of wire cabling prior to installation.