beautypg.com

1 safety characteristic data, Safety characteristic data – Pilz PNOZ m1p base unit User Manual

Page 36

background image

Technical Details

Operating Manual PNOZ m1p (ETH)
20878-EN-12

36

Safety characteristic data

Unit

Operating

mode

EN ISO

13849-1: 2006
PL

EN ISO

13849-1: 2006
Category

EN IEC 62061
SIL CL

EN IEC 62061
PFH

D

[1/h]

EN ISO

13849-1: 2006
T

M

[year]

Logic
CPU

PL e

Cat. 4

SIL CL 3

4,90E-09

20

Expansion

PL e

Cat. 4

SIL CL 3

9,20E-09

20

Input
SC inputs

1-channel

PL d

Cat. 2

SIL CL 2

2,50E-09

20

SC inputs

2-channel

PL e

Cat. 4

SIL CL 3

2,90E-10

20

SC inputs

Short cir-

cuit-forming

safety mats

PL d

Cat. 3

SIL CL 2

1,81E-09

20

SC inputs

1-ch., pulsed

light beam

device

PL e

Cat. 4

SIL CL 3

2,50E-10

20

Cascad. inputs –

PL e

Cat. 4

SIL CL 3

3,10E-10

20

Output
SC outputs

1-channel

PL d

Cat. 2

SIL CL 2

7,00E-09

20

SC outputs

2-channel

PL e

Cat. 4

SIL CL 3

8,60E-10

20

Cascad. out-

puts

PL e

Cat. 4

SIL CL 3

4,91E-10

20

Relay outputs

1-channel

PL c

Cat. 1

-

2,90E-08

20

Relay outputs

2-channel

PL e

Cat. 4

SIL CL 3

3,00E-10

20

All the units used within a safety function must be considered when calculating the safety
characteristic data.

Information
A safety function's SIL/PL values are

not identical to the SIL/PL values of

the units that are used and may be different. We recommend that you use
the PAScal software tool to calculate the safety function's SIL/PL values.

ATTENTION!
It is essential to consider the relay's service life graphs. The relay outputs'
safety-related characteristic data is only valid if the values in the service life
graphs are met.

The PFH value depends on the switching frequency and the load on the relay output. If the
service life graphs are not accessible, the stated PFH value can be used irrespective of the
switching frequency and the load, as the PFH value already considers the relay's B10d val-
ue as well as the failure rates of the other components.

8.1