Pilz PNOZ m1p base unit User Manual
Page 31
Technical Details
Operating Manual PNOZ m1p (ETH)
20878-EN-12
31
Relay outputs
773100
773103
773104
773105
Utilisation category
In accordance
with the standard
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
EN 60947-4-1
Safety contacts,
AC1 at
240 V
240 V
240 V
240 V
Max. current
6,0 A
6,0 A
6,0 A
6,0 A
Max. power
1440 VA
1440 VA
1440 VA
1440 VA
Safety contacts,
DC1 at
24 V
24 V
24 V
24 V
Max. current
6,0 A
6,0 A
6,0 A
6,0 A
Max. power
144 W
144 W
144 W
144 W
Derating of coated
version at an ambi-
ent temperature > 50
°C
Safety contacts,
AC1 at
–
–
240 V
240 V
Max. current
–
–
4 A
4 A
Max. power
–
–
960 W
960 W
Safety contacts,
DC1 at
–
–
24 V
24 V
Max. current
–
–
4 A
4 A
Max. power
–
–
96 W
96 W
Utilisation category
In accordance
with the standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Safety contacts,
AC15 at
230 V
230 V
230 V
230 V
Max. current
3,0 A
3,0 A
3,0 A
3,0 A
Max. power
690 W
690 W
690 W
690 W
Safety contacts,
DC13 (6 cycles/
min) at
24 V
24 V
24 V
24 V
Max. current
3,0 A
3,0 A
3,0 A
3,0 A
Max. power
72 W
72 W
72 W
72 W
Airgap creepage be-
tween
Relay contacts
3 mm
3 mm
3 mm
3 mm
Relay contacts
and other safe cir-
cuits
5,5 mm
5,5 mm
5,5 mm
5,5 mm
Contact fuse protec-
tion, external safety
contacts
In accordance
with the standard
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
EN 60947-5-1
Blow-out fuse,
quick
6 A
6 A
6 A
6 A
Blow-out fuse,
slow
6 A
6 A
6 A
6 A