Technical Details
Operating Manual PNOZ m1p (ETH)
20878-EN-12
34
Environmental data 773100
773103
773104
773105
Protection type
In accordance
with the standard
EN 60529
EN 60529
EN 60529
EN 60529
Mounting (e.g.
cabinet)
IP54
IP54
IP54
IP54
Housing
IP20
IP20
IP20
IP20
Terminals
IP20
IP20
IP20
IP20
Potential isolation 773100
773103
773104
773105
Potential isolation
between
SC output and sys-
tem voltage
SC output and sys-
tem voltage
SC output and sys-
tem voltage
SC output and sys-
tem voltage
Type of potential iso-
lation
Safe separation
Safe separation
Safe separation
Safe separation
Rated surge voltage
2500 V
2500 V
2500 V
2500 V
Potential isolation
between
RL output and sys-
tem voltage
RL output and sys-
tem voltage
RL output and sys-
tem voltage
RL output and sys-
tem voltage
Type of potential iso-
lation
Safe separation
Safe separation
Safe separation
Safe separation
Rated surge voltage
6000 V
6000 V
6000 V
6000 V
Mechanical data
773100
773103
773104
773105
Mounting position
Horizontal on top
hat rail
Horizontal on top
hat rail
Horizontal on top
hat rail
Horizontal on top
hat rail
DIN rail
Top hat rail
35 x 7,5 EN 50022 35 x 7,5 EN 50022 35 x 7,5 EN 50022 35 x 7,5 EN 50022
Recess width
27 mm
27 mm
27 mm
27 mm
Max. cable length
Max. cable length
per input
1,0 km
1,0 km
1,0 km
1,0 km
Sum of individual
cable lengths at
the test pulse out-
put
40 km
40 km
40 km
40 km
Material
Bottom
PPO UL 94 V0
PPO UL 94 V0
PPO UL 94 V0
PPO UL 94 V0
Front
ABS UL 94 V0
ABS UL 94 V0
ABS UL 94 V0
ABS UL 94 V0
cross section of ex-
ternal conductors
with screw terminals
(relay outputs)
1 core flexible
0,5 - 2,5 mm², 22 -
12 AWG
0,5 - 2,5 mm², 22 -
12 AWG
0,5 - 2,5 mm², 22 -
12 AWG
0,5 - 2,5 mm², 22 -
12 AWG
2 core with the
same cross sec-
tion, flexible with-
out crimp connec-
tors or with TWIN
crimp connectors
0,50 - 1,25 mm², 22
- 16 AWG
0,50 - 1,25 mm², 22
- 16 AWG
0,50 - 1,25 mm², 22
- 16 AWG
0,50 - 1,25 mm², 22
- 16 AWG