Pilz PNOZ m1p base unit User Manual
Page 32
Technical Details
Operating Manual PNOZ m1p (ETH)
20878-EN-12
32
Relay outputs
773100
773103
773104
773105
Circuit breaker,
24V AC/DC, char-
acteristic B/C
6 A
6 A
6 A
6 A
Switch-off delay
50 ms
50 ms
50 ms
50 ms
Potential isolation
Yes
Yes
Yes
Yes
Cascading output
as standard output
773100
773103
773104
773105
Number
1
1
1
1
Switching capability
Voltage
24 V
24 V
24 V
24 V
Current
0,2 A
0,2 A
0,2 A
0,2 A
Power
4,8 W
4,8 W
4,8 W
4,8 W
Galvanic isolation
No
No
No
No
Short circuit-proof
Yes
Yes
Yes
Yes
Residual current at
"0"
0,5 mA
0,5 mA
0,5 mA
0,5 mA
Ethernet interface 773100
773103
773104
773105
Number
–
2
2
–
Serial interface
773100
773103
773104
773105
Number of RS232
interfaces
1
–
–
1
Times
773100
773103
773104
773105
Switch-on delay
5,00 s
5,00 s
5,00 s
5,00 s
Supply interruption
before de-energisa-
tion
20 ms
20 ms
20 ms
20 ms
Simultaneity, chan-
nel 1 and 2
3 s
3 s
3 s
3 s
Simultaneity in the
two-hand circuit
0,5 s
0,5 s
0,5 s
0,5 s
Max. Device cycle
time
15 ms
15 ms
15 ms
15 ms
Max. Processing
time for data com-
munication
–
50 ms
50 ms
–
Environmental data 773100
773103
773104
773105
Ambient temperature
In accordance
with the standard
EN 60068-2-14
EN 60068-2-14
EN 60068-2-14
EN 60068-2-14
Temperature
range
0 - 60 °C
0 - 60 °C
-25 - 60 °C
-25 - 60 °C
Forced convec-
tion in control
cabinet off
55 °C
55 °C
–
–
Storage temperature
In accordance
with the standard
EN 60068-2-1/-2
EN 60068-2-1/-2
EN 60068-2-1/-2
EN 60068-2-1/-2
Temperature
range
-25 - 70 °C
-25 - 70 °C
-25 - 70 °C
-25 - 70 °C