beautypg.com

Transfer – LINK Systems OmniLink II Press Automation Control User Manual

Page 125

background image

August 30, 2002 Manual Version 1.0

6.20

angle just before the part is released into the next
stage of the die. The timing for Transfer is
shown in Figure 6.20. The sensor must signal
that the part is present for the entire timing
window. In addition, the sensor must signal that
the part is not present sometime during the press
stroke. If the sensor does signal that a part is
present for an entire press stroke, a sensor failure
is assumed and a stop signal will be issued.

An additional feature of Transfer type inputs is
the delay timer, which is programmed by the
operator. A programmed time of zero forces
ordinary operation of the transfer input as
described above, i.e., if the sensor does not
report the part present through the entire timing
window, a fault will occur immediately. However, if a value other than zero is programmed the channel
input is allowed to signal a missing part for the length of time programmed without a fault occurring. If
the input does not signal a part present before the time expires and the timing window is still in effect, a
fault is generated. This allows the operator to avoid nuisance faults from sensors that 'bounce' open or
closed momentarily. The delay time can range from 0 to 65535 milliseconds (65.535 seconds) in 1
millisecond increments.

The sensor being used to verify part detection can be Normally Off or Normally On. The sensor will
switch from its normal state when the part is being detected. When a Normally Off sensor is being used
to sense part out; the sensor will be Off when the part is not on the sensor, and will be On when the part
is on the sensor. When a Normally On sensor is being used to sense part out; the sensor will be On when
the part is not on the sensor, and will be Off when the part is on the sensor.

Section 6.5.9 Custom

Custom type channels allow the user to define the channel logic. If there is a monitoring situation that
does not fit the logic of the eight standard types, the custom type can be used. This type allows the user
to define a set of logic rules for the channel. The channel’s input will be monitored based upon the
defined rules.

The Custom Rules are:

Detections in the timing window

Enter the timing window On

Enter the timing window Off

Exit the timing window On

Exit the timing window Off

Always On in the timing window

Always Off in the timing window

Off somewhere in the stroke

Off somewhere in the window

270

0

180

90

Part

Part Must Be

Present Through

The Entire Timing

Window

Transfer

Timing Window

Figure 6.19 Transfer Timing