Echelon Mini EVK User Manual
Page 87

1. I cannot compile the MGKeyboard application. When I try to compile
the application, the "Typename 'UCPTfrequency' not found in Device
Resource Files; 'SNVT*', 'SCPT*', 'UNVT*', 'UCPT*' are
reserved [NCC#389]
" error is reported.
• For a TP/FT-10 channel, set the application’s program ID to
9F:FF:FF:05:00:05:04:xx.
• For a PL-20N (power line PL-20 Smart Transceiver with CENELEC protocol
disabled) target channel type, set the application’s program ID to
9F:FF:FF:05:00:05:11:xx.
• For a PL-20C (power line PL-20 Smart Transceiver with CENELEC protocol
enabled) target channel type, set the application’s program ID to
9F:FF:FF:05:00:05:10:xx.
• See the header comment in the MGKeyboard.nc file for more details.
2. My application will not link to the ISI library. The linker reports
"cannot relocate segment..." when I try to add the library to my
application.
• Make sure you link with the correct version of the ISI library. See the header
comment in your application source file for recommendations.
• The memory requirements of your application and all required libraries
together might simply exceed the amount of available memory. See chapter 8,
Memory Management, in the Neuron C Reference Guide of a list of
suggestions What to Try When a Program Doesn’t Fit in a Neuron Chip.
3. My application will not link to the ISI library. The linker reports
"symbol not found..." when I try to build my application.
• Make sure you link with the correct version of the ISI library. The Neuron
linker does not automatically link the application with the ISI library; you
must provide a reference to that library through the Libraries section in the
Mini Application.
• Make sure the reference to the offending symbol name is spelled correctly in
your source code. Remember that symbol names in the C language family
are case-sensitive.
4. The Mini Application reports error #10 when I load an application
into my device.
The application cannot be loaded into the device, as the device does not contain
the amount of memory required to load the application. This error will occur if
you attempt to load the MGDemo application into an FT 3120 or PL 3120
Evaluation Board.
5. What can I do to improve application load-times on power line
channels?
Mini EVK User’s Guide