Echelon LonPoint Application and Plug-In User Manual
Page 9
![background image](/manuals/735719/9/background.png)
The LonPoint Application and Plug-in Guide
1-3
6
Analog Input
(AI)
Senses current, voltage,
or resistance inputs
Measure temperature,
pressure, humidity,
velocity, level
7
Analog Output
(AO)
Drives current, voltage,
or resistance analog
outputs
Variable speed drive
control; valve control;
damper control
8
Analog
Function
Block (AFB)
Performs functions on
two analog values and a
digital value such as add,
subtract, multiply, divide,
greater than, less than,
enthalpy, and comparison
Deadband thermostat,
heating/cooling
optimization
9
PID Controller
(PID)
Performs closed-loop
control
Pressure, temperature, or
position loops
10/11
Real Time
Clock (RTC)
Maintains date, day of
week, and time of day
Non-volatile system time
source
10/11
Event
Scheduler (ES)
Schedules system events
Scheduler with occupied
and unoccupied periods,
daily, weekly, holiday
schedules
10/11
State Machine
(SM)
Controls system state
Sequence of operations
controller
12
Type
Translator
Converts network
variable data types
Interface between
incompatible devices
13
Data Logger
Logs periodic data based
on exceptional data
values or large changes in
data value.
Logging periods of
extreme
temperature/rapid
fluctuations.
14
Node Object
Management commands
for a device
Putting devices into
Override. Getting device
status.
The LonPoint functional blocks are loaded into the LonPoint devices as listed below.
Table 1.2 Assignment of LonPoint Functional Blocks to LonPoint Devices
LonPoint Device
Functional Block
Quantity per Device
DI-10
Node Object
Digital Input
Digital Encoder
Analog Function Block
Type Translator
1
4
2
4
6
DO-10
Node Object
Digital Output
Digital Encoder
Analog Function Block
Type Translator
1
4
2
2
6
DIO-10
Node Object
Digital Input/Counter
Digital Output
Digital Encoder
Analog Function Block
1
2
2
2
2