Echelon LonPoint Application and Plug-In User Manual
Page 160
![background image](/manuals/735719/160/background.png)
11-14
Schedule Keeper Utility
To change the format type of the network variables used in these equations,
follow these steps:
1. Open the launch file which is to use different unit formats with a text editor
such as Notepad.
2. Each System Parameter has the following format:
SystemParameter=
For Example:
SystemParameter=MaxTemp,3
3. Add the format names to the system parameters which are to have a
different format. For example, to have the parameter MaxTemp of SNVT type
SNVT_temp_f
above formatted in degrees Farenheit, you would modify the
string to read as follows:
SystemParameter=MaxTemp,3,SNVT_temp_f
The format specifier SNVT_temp_f will find the current default format for
SNVT_temp_f
, which will be SNVT_temp_f#US if you installed US units format
files, or SNVT_temp_f#SI if you installed System Internationale units format
files.