Digital encoder – Echelon LonPoint Application and Plug-In User Manual
Page 51
![background image](/manuals/735719/51/background.png)
The LonPoint Application and Plug-in Guide
5-3
Digital Encoder
This tab appears as follows:
This tab displays the flow of data through the Digital Encoder functional block.
This tab contains the following fields:
Delay
Specifies the amount of time the digital inputs must
stay constant before they are processed. The value
must be between zero and 48 days, 23 hours, 59
minutes, 59 seconds, and 999 milliseconds. To change
the value, click the button to the right of the time
value to be changed and enter the new values to be
used for the delay. Set this field to zero to disable the
delay function.
Digital Output Override
Selects the value that will be sent on the
Digital_Out
network variable when the functional
block is put into override.
Mode Output Override
Selects the value that will be sent on the Mode_Out
network variable when the functional block is put
into override.