Service (cont’d), 2 troubleshooting (cont’d), Figure 46 - pressure switch troubleshooting guide – Reznor VR Unit Installation Manual User Manual

Page 45: Figure 45 - basic troubleshooting guide

background image

Form I-VR, P/N 205202 R13, Page 44

Is the Pressure

Switch Stuck Open, LED

Fault - 1 FLASH

OR

Stuck Closed, LED Fault -

2 FLASHES

?

2 FLASHES

- Is there 24VAC at

COM on pressure

switch?

Is there 24VAC at

N.O. contact on pressure

switch?

Replace pressure swtich. It

is stuck closed if

combustion air blower is

not running.

Is there 24VAC at

PS2 terminal on DSI

control board?

Mis-wired; check

wiring from pressure

swtich to DSI control

board.

Replace DSI

control

board.

Check wire continuity

to pressure switch.

1 FLASH - Is the

combustion air blower

running?

Is there

24VAC at COM contact

on the pressure

switch?

Is there 24VAC at

N.O. contact on pressure

switch?

Is there

24VAC at PS2 on

DSI control board?

Replace DSI

control board.

Check wiring from

pressure switch to

control.

Replace pressure

switch.

Check wiring

continuity to

pressure switch.

Is there correct line

VAC at the combustion air

blower motor?

Replace combustion air

blower motor.

Is there correct

line VAC at IND on DSI

control board?

Check wire continuity

from DSI control board

to combustion air

motor.

Is there

24VAC at "W" on

DSI control board?

Replace DSI control

board.

No call for heat or

check wiring to and

from thermostat.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

STUCK CLOSED

STUCK OPEN

FIGURE 46 -

Pressure Switch

Troubleshooting

Guide

Is the gas

supply turned

on?

Is the gas supply

pressure correct (Refer to

Paragraph 6.3)?

Is the main

electrical supply on?

Is the correct

voltage being supplied.

Rated Acceptable Ranges:

115V - 105 to 130V

208V - 200 to 235V

230V - 210 to 250V

?

Does the

combustion air

blower operate (listen or look

into combustion air

inlet.)?

Is the pressure

switch closing (if the

thermostat is cycled, you should

hear the valve opening and

closing)?

Is the burner

lit (look through

viewport)?

Check the wiring to

the gas valve. If OK,

replace gas valve.

Refer to Ignition

Troubleshooting

Guide,

FIGURE 44.

Refer to pressure

switch

Troubleshooting

Guide,

FIGURE 46.

Is voltage

present at motor

terminals?

Replace

combustion air

blower motor.

Is voltage present

at IND on the DSI control

board?

Check wire continuity

from DSI control board

to combustion air

blower motor.

Is there 24VAC at

"W" on the DSI control

board?

Replace DSI

control board.

No call for heat or

check wiring to and

from the thermostat.

Correct improper

supply voltage.

Turn on main

electrical supply.

Correct supply prssure by

adjusting field-supplied

pressure regulator or add a

pressure regulator as

appropriate.

Open all manual gas valves

in the supply line to the

heater. Rotate the knob on

the combination valve to

the "ON" position.

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

YES

NO

FIGURE 45 -

Basic

Troubleshooting

Guide

10.2 Troubleshooting (cont’d)

10. Service (cont’d)