PROBLEM
PROBABLE CAUSE
REMEDY
Burner cycles
on and off
1. Gas pressure too high or too low.
1. See Gas Supply Pressure Table, Paragraph 6.3.
2. DSI control board not grounded.
2. Make certain DSI control board is grounded to furnace chassis.
3. Faulty DSI control board.
3. If 24 volt is available to the DSI control board and all other causes have
been eliminated, replace board.
4. Combustion air proving switch
not closing.
4.
a) Make sure unit is properly vented.
b) Remove obstructions from vent.
c) Replace faulty tubing to pressure switch.
5. Faulty combustion air proving switch.
5. Replace combustion air proving switch.
6. Spark electrode assembly grounded.
6. Be certain spark electrode assembly lead is not grounded or insulation
or ceramic is not cracked. Replace as required.
7. Cracked ceramic at spark electrode assembly. 7. Replace spark electrode assembly.
No heat (Heater
Operating)
1. Incorrect valve outlet pressure.
1. Check valve outlet pressure. See Rating plate for valve outlet pressure.
2. Improper thermostat location or adjustment.
2. See thermostat manufacturer’s instructions.
Blower motor
will not run
1. Circuit open.
1. Check wiring and connections.
2. Defective DSI control board.
2. Replace board.
3. Defective motor.
3. Replace motor.
Blower motor
turns on and
off while burner
is operating
1. Motor overload device cycling on and off.
1. Check motor load against motor rating plate. Replace motor if needed.
Blower motor
cuts out on
overload
1. Low or high voltage supply.
1. Correct electric supply.
2. Defective motor.
2. Replace motor.
3. Poor air flow.
3. Clean motor and blower.
4. Defective bearing.
4. Replace motor.
Trial for
Ignition
Call for Heat
Is there a
spark across gap at
ignitor?
Does gas
ignite?
Is the
spark ignitor
corroded?
Clean spark
ignitor.
Is the spark
ignitor in flame
correctly?
Replace spark
ignitor.
Repositon
spark ignitor.
Is gas flowing?
Is the ignitor
position correct in the
gas flow?
Check gas pressure
and supply voltage. If
either are low, correct
and repeat startup.
Reposition spark
ignitor.
Is there
24VAC at the gas
valve?
Is there 24VAC
from gas valve output on
DSI control board to
chassis?
Check wiring
and connections
to gas valve.
Replace DSI
control board.
Replace gas
valve.
Is there spark
voltage at DSI control
board?
Check high
voltage wire
continuity.
Is there 24V
to "W" to power
control?
Replace DSI
control board.
Check wiring
and/or 24VAC
transformer output.
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
YES
NO
NO
YES
YES
NO
YES
NO
YES
NO
FIGURE 44 - Ignition Troubleshooting Guide
(Assumes pressure switch is actuated.)