beautypg.com

Mechanical (cont’d), 2 assemble and suspend the heater (cont’d) – Reznor VR Unit Installation Manual User Manual

Page 13

background image

Form I-VR, P/N 205202 R13, Page 12

FIGURE 9 -

Wire Reflector

Retainer,

Hanger Bar,

and Tube

Bracket

Wire Reflector

Retainer and

Hanger Bar

Tube Bracket and Hardware (U-bolt and nuts) -

wire retainer hooks through ends of bracket

FIGURE 10 -

Bottom View

with Wire

Reflector

Retainer and

Tube Bracket

Installed

(Hanger bar is

not illustrated.)

Tube

Bracket

“Hook” wire reflector

retainer through

ends of tube bracket.

U Bolt

Nuts

3. Suspension of the Combustion Chamber Tube

Slide the hanger bar up over the reflector retainer wire. Attach an “S” hook

at the center hole in the bar. Attach a turnbuckle or chain to the “S” hook.

Using a turnbuckle is recommended for leveling.

If the installation is going to be horizontal and a turnbuckle has been used,

close the “S” hooks. If the reflector is going to be angled or there is no turn-

buckle, leave the “S” hooks open until after the system is leveled.

6. Mechanical

(cont’d)

FIGURE 11 - Suspend the Burner Control Box (with Combustion Chamber Tube attached)

9-1/4”(235mm)

15-3/32”

(383mm)

Height

of Box

Including

Hangers

24” (610mm) Distance between

Suspension Points

Attached combustion

chamber tube.

Chains should be plumb with

each suspension point.

Suspension

Point

Suspension

Point

Minimum

12” (305mm)

A =

12”

(305mm)

Minimum

A + A/4

Burner/Control

Box End View

Burner/Control Box

Side View with Combustion

Chamber Tube Attached.

Install a tube bracket

with hanger on each

end of the combustion

chamber tube. Suspend

from both hanger bars.

2. Suspension of the Burner/Control Box (See FIGURE 11.)

Attach the four “S” hooks to the hanger brackets on the burner control box.

Suspend the box as illustrated in

FIGURE 11. Keep all chains plumb with

the hanger and suspension point.

NOTE: Use of turnbuckles is recom-

mended for leveling.

6.2 Assemble and

Suspend the

Heater (cont’d)

6.2.2 Suspend the Assembled Burner/Control Box and

Combustion Chamber Tube (cont’d)

NOTE: One “hook” of the

wire retainer is bent 75° and

the other 45°. If the reflector

is going to be rotated, be

sure the side with the 45°

bend will be at the lower

side.