beautypg.com

Reznor VR Unit Installation Manual User Manual

Page 24

background image

Form I-VR, P/N 205202 R13, Page 23

But if adjustment is required, set pressure to correct settings by turning the

regulator screw IN (clockwise) to increase pressure. Turn regulator screw OUT

(counterclockwise) to decrease pressure.

Remove manometer, replace the cap, and check for leak at pressure tap.

CAUTION: DO NOT bottom out the gas valve regulator adjusting

screw. This can result in unregulated manifold pressure causing

excess overfire and heat exchanger failure.

1. Determine the required valve outlet pressure for the elevation where the

heater will be operating. If unsure of the elevation, contact the local gas

supplier.

Instructions for High

Altitude Derate

3. Turn the knob or switch on the valve to “ON”. Remove the cap from the

pressure adjusting screw and adjust the gas train pressure to the pressure

selected from the table above. Adjust pressure by turning the regulator

screw IN (clockwise) to increase pressure or OUT (counterclockwise) to

decrease pressure.

4. Turn up the thermostat. Cycle the burner once or twice to properly seat the

adjustment spring in the valve.

Re-check the pressure(s). When the outlet pressure is right for the installa-

tion, remove the manometer and replace the cap.

Check for leak at the pressure tap fitting.

5. With the heater operating, determine that the inlet pressure to the valve for

natural gas is between 4.5” and 14” w.c. for Sizes 50-150 and between 6”

Derate is by Valve

Outlet Pressure

Adjustment for High

Altitude Operation

This adjustment can

only be done after the

heater is in operation.

It is included in the

startup procedures.

NOTE: Sizes 50-175 - If

elevation is above 6000

ft (1830M), a high altitude

pressure switch should

have been installed; see

Paragraph 6.1.

FIGURE 24 - Gas

Valve (two styles)

showing Outlet

Pressure Tap and

Adjustment Locations

1/8” Output

Pressure Tap

Inlet

Pressure

Tap

Output

Adjustment Screw

Manifold Pressure Settings by Altitude for the United States

Altitude

Natural Gas (“ w.c.)

Propane (“ w.c.)

Feet

Meters

50, 75, 100, 125,

150

175 & 200

50, 75, 100, 125, 150,

175, 200

0 - 2000

0 - 610

3.5

5.0

10.0

2001 - 3000

611 - 915

2.7

3.9

7.7

3001 - 4000

916 - 1220

2.5

3.5

7.1

4001 - 5000

1221 - 1525

2.2

3.2

6.4

5001 - 6000

1526 - 1830

2.0

2.9

5.8

6001 - 7000

1831 - 2135

1.8

2.6

5.2

7001 - 8000

2136 - 2440

1.6

2.3

4.6

8001 - 9000

2441 - 2745

1.4

2.0

4.1

9001 - 10000

2746 - 3051

1.3

1.8

3.6

Manifold Pressure Settings by Altitude for Canada

Altitude

Natural Gas (“ w.c.)

Propane (“ w.c.)

Feet

Meters

50, 75, 100, 125,

150

175 & 200

50, 75, 100, 125, 150,

175, 200

0 - 2000

0 - 610

3.5

5.0

10.0

2001 - 4500

611 - 1373

2.8

4.1

8.1

2. Locate the 1/8” output pressure tap on the valve (See FIGURE 24). Turn

the knob or switch on the valve to “OFF”. Connect a manometer to the 1/8”

pipe outlet pressure tap in the valve. Use a water column manometer that

is readable to the nearest tenth of an inch.

1/8” Outlet

Pressure

Tap

Inlet

Pressure

Tap

Adjust Outlet

Pressure