Form I-VR, P/N 205202 R13, Page 16

FIGURE 17A - Examples of configurations

with the exhaust heat exchanger tube

adjacent to a straight heat exchanger.

FIGURE 17B - Examples of configurations that require more than three turbulator strips

and have the exhaust heat exchanger tube adjacent to an “L” or U” heat exchanger tube.

To install turbulator:

1) Insert a turbulator section into the exhaust heat

exchanger tube.

3) Interlock turbulator sections as they are inserted

(See

FIGURE 16B).

4) Continue until all required sections are in place.

Slide all turburlator sections

into exhaust heat exchanger tube

.

Slide three turbulator sections into

the end of exhaust heat exchanger tube.

Slide two turbulator sections

into heat exchanger tube before “U” or “L”.

To install turbulator:

1) Before attaching the “U” or “L” tube, insert two

interlocked turbulator sections (See

FIGURE

16B) into the last straight tube.

2) Use compression couplings to attach the “U” or

“L” heat exchanger tube to the straight tube and

to the exhaust heat exchanger tube.

3) Insert three interlocked turbulator sections into

the exhaust heat exchanger tube.

6.2.4 Install

Reflectors and

Optional Side Shield

and/or End Covers

Straight Tube
Reflector Installation
Instructions

WARNING: Do not

operate heater

without reflectors.

See Hazard Inten-

sity Levels, page 2.

Reflectors are shipped with the tubes. Clips and screws for length of system

are included in the tube package hardware bag.

FIGURE 18 -

Reflector for

Straight Tubes

Parts/Tools Needed: Clips and screws from the tube package hardware bag

(see Paragraph 3), 1/8” drill, 5/16” nut driver
1. Before installing reflectors, check a), b), c) and d). If needed, adjust or

add tube bracket or suspension point to comply with these requirements.

a) The combustion chamber tube must have two suspension points.

b) Each heat exchanger tube must have at least one suspension point.

c) There must be a suspension point within 12” (305mm) of every coupler.

d) All chains must be plumb with the suspension point.

2. Before installing reflectors, read the instructions to understand the differ-

ence between

NON-SLIP and SLIP reflector overlaps. Installed reflectors

MUST comply with the following.

• No more than two consecutive NON-SLIP overlaps on a straight

system.

• No more than four consecutive NON-SLIP overlaps in a section

containing a

single “U” or “L” tube reflector. NOTE: Two of the four

6. Mechanical

(cont’d)

6.2 Assemble and Suspend the Heater (cont’d)

6.2.3 Install the Heat Exchanger Tubes and Turbulator Strip

Sections (cont’d)

Turbulator Requirements (cont’d)

CAUTION: If the reflectors have a protective film, remove

the protective film before installing reflectors.