beautypg.com

Electrical and wiring -32, Electrical and wiring – Reznor VR Unit Installation Manual User Manual

Page 32

background image

Form I-VR, P/N 205202 R13, Page 31

Outside Combustion

Air Pipe Length Table

Combustion Air Inlet

Kit, Option DE2

If the air inlet terminal is located adjacent to the exhaust terminal, the terminals

must be separated by a minimum distance of three feet (.9M). The only excep-

tion is when the air inlet is located directly below the horizontal vent cap. The

required clearance between an air inlet terminal located directly below the vent

cap is 18 inches (457mm) as illustrated in

FIGURE 27B. See FIGURES 26B

and 27B in Paragraph 6.4.1 for illustrations and clearance requirements of an

air inlet terminal located adjacent to the heater vent terminal.

7. Electrical and Wiring

All electrical wiring and connections, including electrical grounding MUST

be made in accordance with the National Electric Code NFPA No. 70 (latest

edition) or, in Canada, the Canadian Electrical Code, CSA Standard C22.1.

The installer should also be aware of any local ordinances or gas company

requirements that might apply. The heater must be electrically grounded and

connected to a separately fused circuit with a disconnect as required by the

National Electrical Code.

Check the rating plate on the heater for the supply voltage and current require-

ments. A dedicated line voltage supply with disconnect switch should be run

1. Air from inside building -- openings 1 square inch free area per 1000

BTUH. Never less than 100 square inches free area for each opening. See

(1) in

FIGURE 30.

2. Air from outside through duct -- openings 1 square inch free area per

2000 BTUH. See (2) in

FIGURE 30.

3. Air direct from outside -- openings 1 square inch free area per 4000

BTUH. See (3) in

FIGURE 30.

NOTE: For further details on supplying combustion air to confined space, see

National Fuel Gas Code Z223.1 (latest edition).
If directly piped outside combustion air is required, use optional inlet air

kit, Option DE2. Follow the instructions included with the kit. The inlet air pipe

should be of a noncorroding material. The maximum length of the inlet air pipe

must not exceed the length shown in the Table below.
If the inlet air pipe passes through moisture-laden air, insulation or double-wall

tubing may be needed to prevent condensation on the outside of the pipe. Use

the combustion air inlet cap supplied with the option kit. A different type of com-

bustion air inlet cap could cause nuisance problems and/or unsafe operating

conditions.

Maximum Length of Outside Combustion Air Inlet Pipe

Type of Inlet

Air Pipe

BTUH

Size

Hz

Maximum

Length

Equivalent Length for

90° Elbow

45° Elbow

* 4” Smooth Wall

50, 75, 100

50 or 60

80 ft (24.3M)

10 ft (3M)

5 ft (1.5M)

125

60 ft (18.3M)

10 ft (3M)

5 ft (1.5M)

150

60

5” Smooth Wall

150

50

175

50 or 60

200

60

* 4” Corrugated

or Flexible

50, 75, 100

50 or 60

40 ft (12.2M)

N/A

N/A

125

30 ft (9.1M)

N/A

N/A

150

60

5” Corrugated or

Flexible

150

50

175

50 or 60

200

60

*Assumes the use of three feet (.9M) of flexible pipe at the combustion air inlet on the burner/

control box

WARNING: If

you turn off or

disconnect the

electrical power

supply, turn off the

gas. See Hazard

Levels, page 2.