0 roof curbs for models ydha, ydma, ydsa, 1 downflow roof curbs – Reznor ADFH Option - Installation - Roof Curbs Assembly User Manual
Page 32

Form I-OPT-C, Page 32
7.1 Downflow Roof
Curbs
Both Option CJ31 and CJ34 are 16" (406mm) high roof curbs designed for vertical
(down) discharge. These curbs include integral cross supports for supply air and
optional return air ductwork.
Suppl
y
Air
Return
Air
Downflow Curb Option CJ31 or
CJ34
2x6
Wood
Nailer
Insulation
16”
(406mm)
Cross-Section
View
(Control End
of Unit)
(Inlet Hood End)
(Condenser Side of Unit - Base extends
30” / 761mm beyond this side of c
urb.)
Option
Model and Size
Cabinet
Size
A
B
C
D
E**
F**
G
H
(Outside of Curb Rails) (Area Inside the Curb*)
CJ31
No Energy
Wheel
YDHA & YDMA, 060,
090, 120, 150
1
119-11/16
(3040)
43-7/16
(1103)
115-15/16
(2945)
39-11/16
(1008)
31
(787)
17
(432)
25-3/4
(654)
14-29/32
(379)
YDHA & YDMA, 180,
210, 240YDSA 120, 150
2
123-11/16
(3141)
50-11/16
(1287)
119-15/16
(3046)
46-15/16
(1192)
31
(787)
19
(483)
25-13/16
(656)
18-13/16
(478)
YDHA & YDMA, 300,
360 YDSA 180, 210
3
154-11/16
(3929)
63-11/16
(1618)
150-15/16
(3834)
59-15/16
(1522)
31
(787)
21
(533)
28
(711)
28-7/32
(717)
CJ34
With
Energy
Wheel
YDHA & YDMA, 060,
090, 120, 150
1
128
(3251)
43-7/16
(1103)
124-1/4
(3156)
39-11/16
(1008)
31
(787)
17
(432)
25-3/4
(654)
23-1/4
(591)
YDHA & YDMA, 180,
210, 240; YDSA 120,
150
2
132
(3353)
50-11/16
(1287)
128-1/4
(3257)
46-15/16
(1192)
31
(787)
19
(483)
25-13/16
(656)
27-1/8
(689)
YDHA & YDMA, 300,
360; YDSA 180, 210
3
154-11/16
(3929)
63-11/16
(1618)
150-15/16
(3834)
59-15/16
(1522)
31
(787)
21
(533)
28
(711)
28-7/32
(717)
FIGURE 13A - Layout, Dimensions, and Weights of Option CJ31 & CJ34 Roof Curbs
Dimensions for Options CJ31 & CJ34 - inches (mm)
Curb
Layout
* Area enclosed by the roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible
materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R”
value of at least 5. If area within curb is left open, higher radiated sound levels may result.
NOTE: If installing a unit with a high
efficiency, condensing gas-fired heat section, the area within the curb must be left open.
** When cutting only duct openings, cut “E” & “F” dimensions 1/4” (6.4mm) in from duct opening to allow clearance. Cut the curb
rail sides of the duct opening(s) parallel to the curb rail. For Cabinet Size 1, measure a maximum of 1-1/2” (38mm) from the side
rail. For Cabinet Size 2, measure a maximum of 3/4” (19mm) from the side rail. For Cabinet Size 3, measure a maximum of
1-1/4"(32mm) from the side rail.
7.0 Roof Curbs for
Models YDHA,
YDMA, YDSA
Two styles of curbs are available. Option CJ31 and CJ34 in Paragrapgh 7.1 are for
downflow air applications. Option CJ48 and CJ55 in Paragraph 7.2 are for horizontal
air flow applications.
Return
Air
(DxF)
Supply
Air
(DxE)
Unit
Airflow
A
B
D
E
F
Top View
C
H
G
Weights of Downflow Roof Curb Option CJ31 and CJ34 by Cabinet Size
Roof
Curb
Cabinet 1
Cabinet 2
Cabinet 3
lbs
kg
lbs
kg
lbs
kg
Option
CJ31
237
108
257
117
322
146
Option
CJ34
248
112
268
122
322
146
- RCB Option - Installation - Roof Curbs Assembly RDB Option - Installation - Roof Curbs Assembly RDC Option - Installation - Roof Curbs Assembly RDCB Option - Installation - Roof Curbs Assembly RDCC Option - Installation - Roof Curbs Assembly RDDB Option - Installation - Roof Curbs Assembly RCC Option - Installation - Roof Curbs Assembly RDDC Option - Installation - Roof Curbs Assembly RECB Option - Installation - Roof Curbs Assembly RECC Option - Installation - Roof Curbs Assembly REDB Option - Installation - Roof Curbs Assembly REDC Option - Installation - Roof Curbs Assembly RDF Option - Installation - Roof Curbs Assembly RDH Option - Installation - Roof Curbs Assembly REH Option - Installation - Roof Curbs Assembly RHH Option - Installation - Roof Curbs Assembly RXH Option - Installation - Roof Curbs Assembly RPB Option - Installation - Roof Curbs Assembly RPBL Option - Installation - Roof Curbs Assembly RPDBL Option - Installation - Roof Curbs Assembly YDSA Option - Installation - Roof Curbs Assembly YDMA Option - Installation - Roof Curbs Assembly YDHA Option - Installation - Roof Curbs Assembly RBL Option - Installation - Roof Curbs Assembly ADF Option - Installation - Roof Curbs Assembly