beautypg.com

0 roof curbs for models ydha, ydma, ydsa, 1 downflow roof curbs – Reznor ADFH Option - Installation - Roof Curbs Assembly User Manual

Page 32

background image

Form I-OPT-C, Page 32

7.1 Downflow Roof

Curbs

Both Option CJ31 and CJ34 are 16" (406mm) high roof curbs designed for vertical

(down) discharge. These curbs include integral cross supports for supply air and

optional return air ductwork.

Suppl

y

Air

Return

Air

Downflow Curb Option CJ31 or

CJ34

2x6

Wood

Nailer

Insulation

16”

(406mm)

Cross-Section

View

(Control End

of Unit)

(Inlet Hood End)

(Condenser Side of Unit - Base extends

30” / 761mm beyond this side of c

urb.)

Option

Model and Size

Cabinet

Size

A

B

C

D

E**

F**

G

H

(Outside of Curb Rails) (Area Inside the Curb*)

CJ31

No Energy

Wheel

YDHA & YDMA, 060,

090, 120, 150

1

119-11/16

(3040)

43-7/16

(1103)

115-15/16

(2945)

39-11/16

(1008)

31

(787)

17

(432)

25-3/4

(654)

14-29/32

(379)

YDHA & YDMA, 180,

210, 240YDSA 120, 150

2

123-11/16

(3141)

50-11/16

(1287)

119-15/16

(3046)

46-15/16

(1192)

31

(787)

19

(483)

25-13/16

(656)

18-13/16

(478)

YDHA & YDMA, 300,

360 YDSA 180, 210

3

154-11/16

(3929)

63-11/16

(1618)

150-15/16

(3834)

59-15/16

(1522)

31

(787)

21

(533)

28

(711)

28-7/32

(717)

CJ34

With

Energy

Wheel

YDHA & YDMA, 060,

090, 120, 150

1

128

(3251)

43-7/16

(1103)

124-1/4

(3156)

39-11/16

(1008)

31

(787)

17

(432)

25-3/4

(654)

23-1/4

(591)

YDHA & YDMA, 180,

210, 240; YDSA 120,

150

2

132

(3353)

50-11/16

(1287)

128-1/4

(3257)

46-15/16

(1192)

31

(787)

19

(483)

25-13/16

(656)

27-1/8

(689)

YDHA & YDMA, 300,

360; YDSA 180, 210

3

154-11/16

(3929)

63-11/16

(1618)

150-15/16

(3834)

59-15/16

(1522)

31

(787)

21

(533)

28

(711)

28-7/32

(717)

FIGURE 13A - Layout, Dimensions, and Weights of Option CJ31 & CJ34 Roof Curbs

Dimensions for Options CJ31 & CJ34 - inches (mm)

Curb

Layout

* Area enclosed by the roof curb must comply with clearance to combustible materials. If the roof is constructed of combustible

materials, area within the roof curb must be ventilated, left open, or covered with non-combustible material which has an “R”

value of at least 5. If area within curb is left open, higher radiated sound levels may result.

NOTE: If installing a unit with a high

efficiency, condensing gas-fired heat section, the area within the curb must be left open.

** When cutting only duct openings, cut “E” & “F” dimensions 1/4” (6.4mm) in from duct opening to allow clearance. Cut the curb

rail sides of the duct opening(s) parallel to the curb rail. For Cabinet Size 1, measure a maximum of 1-1/2” (38mm) from the side

rail. For Cabinet Size 2, measure a maximum of 3/4” (19mm) from the side rail. For Cabinet Size 3, measure a maximum of

1-1/4"(32mm) from the side rail.

7.0 Roof Curbs for

Models YDHA,

YDMA, YDSA

Two styles of curbs are available. Option CJ31 and CJ34 in Paragrapgh 7.1 are for

downflow air applications. Option CJ48 and CJ55 in Paragraph 7.2 are for horizontal

air flow applications.

Return

Air

(DxF)

Supply

Air

(DxE)

Unit

Airflow

A

B

D

E

F

Top View

C

H

G

Weights of Downflow Roof Curb Option CJ31 and CJ34 by Cabinet Size

Roof

Curb

Cabinet 1

Cabinet 2

Cabinet 3

lbs

kg

lbs

kg

lbs

kg

Option

CJ31

237

108

257

117

322

146

Option

CJ34

248

112

268

122

322

146