beautypg.com

0 roof curbs for preeva, Models rdh, reh, rhh, & rxh, Models rdh, reh, rhh, and rxh – Reznor ADFH Option - Installation - Roof Curbs Assembly User Manual

Page 19

background image

Form I-OPT-C, P/N 132900 R17, Page 19

44-1/8”

(1121mm)

- inside

of curb

47-7/16”

(1205mm)

- outside

of rails

Rail Width

1-21/32”

(42mm)

Rail Width

1-21/32”

(42mm)

Outside Air Inlet Location

(on side of unit)

TOP VIEW of Assembled

ROOF CURB

Exhaust Air

Outlet Location

(on side of unit)

Supply Air

Opening

18-7/32” x 8-1

1/64”

(463mm x 2

08mm)

64-5/32” (1629mm) - inside of curb

67-15/32” (1713mm) - outside of rails

21-1/2”

(546mm)

Return Air Opening

19-51/64” x 8-11/64”

(503mm x 208mm)

22-1/4” (565mm)

Horizontal Return

Air Opening

Location on

Side of Unit

Supply

Air Opening

Location on

Side of Unit

FIGURE 6D - Dimensions - Option CJ3C Roof Curb and Duct Opening Dimensions, Z Series

Slide return

air and

supply

ductwork

down from

the top

and attach

to duct

flanges.

Approximate

weight of

roof curb is

196 lbs

(89 kg).

Inlet

Air

Drain

Electrical

Entrance

Installed Option CJ3 Curb

Model ZQYRA

FIGURE 6C - Correct

Orientation of

Ventilation Unit to

Roof Curb when using

Vertical Ductwork

IMPORTANT: Verify that the unit

is being placed on the curb in

the correct airflow orientation.

Reminder NOTES:
Curb is designed for ductwork to

be installed from the top prior to

setting unit on the curb.
Always apply sealant tape to top of

curb rails before placing unit.

4.0 Roof Curbs for

PreevA

®

Models

RDH, REH, RHH,

and RXH

Roof Curb Option Packages for Models RDH, REH, RHH, and RXH include corner

assembly hardware and factory-assembled curb pieces. All other installation compo-

nents are field supplied

COMPONENTS of Roof Curb Packages for PreevA

®

Models

NOTE: If a Model RDH or REH replaces a Reznor

®

Model Series RGB or RPB unit,

curb adapters are available; contact your distributor for information.

CAUTION: Before installation, recheck to be sure that the correct curb

has been ordered. Be sure that the curb selected matches the unit

ordered. Verify the dimensions of the curb received with the appropriate

dimension table (pages 22-24).