c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 94 of 116
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
TSEG1
0
63
- - -
31
reserved
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
TSEG2
1
7
- - -
7
reserved
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
SJW
0
3
- - -
0
reserved
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
BTR(1)
1
15
- - -
15
reserved
Diagnostic
FRAM
parameter available in read only modality
non volatile memory status
ok
= not in error
err
= in error
Diagnostic
5V Ratio
parameter available in read only modality
status of the power supply voltage of the
ratiometric transducers
ok
= not in error
err
= in error (because of out of
range voltage)
Diagnostic
24V Sensor
parameter available in read only modality
status of the power supply voltage of the
0-20 mA / 4-20 mA / 0-10 V transducers
ok
= not in error
err
= in error (because of out of
range voltage)
Debug
[ Algo ]
Main time
parameter available in read only modality
main cycle time of the application software
(in milliseconds)
Int. time
parameter available in read only modality
interrupt cycle time of the application
software (in milliseconds)
Debug
[ CAN bus ]
rx
parameter available in read only modality
number of packages in transmission
tx
parameter available in read only modality
number of packages in reception