NO8
normally open contact digital output 8
NC8
normally closed contact digital output 8
The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
The maximum current allowed on the loads is 10 A.
ANALOG OUTPUTS
Analog outputs 1, 2 and 3.
Terminal
Meaning
VDC
power supply driving analog output 1 (24 VDC, 50 mA max.)
AO1
analog output 1 (PWM signal)
GND
ground
AO2
analog output 2 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)
AO3
analog output 3 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)
The maximum length of the connecting cables of the PWM analog output is 1 m (3.280 ft); the one of the connecting cables of
the 0-20 mA / 4-20 mA / 0-10 V analog outputs is instead of 30 m (98 ft).
For the settings about the analog outputs look at chapter 6 “CONFIGURATION”.
The analog output 1 is usable on condition that the controller is powered in alternate current and the phase powering the controller is the
same powering the user driven by the output.
DIGITAL INPUTS
Digital inputs 1, 2, 3, 4, 5, 6 and 7.
Terminal
Meaning
DI1
digital input 1
DI2
digital input 2
DI3
digital input 3
DI4
digital input 4
DI5
digital input 5
DI6
digital input 6
DI7
digital input 7
COM
common digital inputs