EVCO EPH4EXP Hardware manual User Manual
Page 31

EVCO S.p.A.
c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 31 of 116
DI7
digital input 7
COM
common digital inputs
The maximum length of the connecting cables of the digital inputs is 100 m (328 ft).
The digital inputs can be used on condition that they are powered at 24 VAC / DC.
ANALOG INPUTS
Analog inputs.
Each analog input is configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric /
0-10 V transducers.
Terminal
Meaning
GND
ground
AI1
analog input 1
AI2
analog input 2
AI3
analog input 3
AI4
analog input 4
AI5
analog input 5
GND
ground
+5V
power supply 0-5 V ratiometric transducers (5 VDC, 40 mA max.)
+24V
power supply 0-20 mA / 4-20 mA / 0-10 V transducers (24 VDC, 120 mA max.)
The maximum length of the connecting cables of the analog inputs and the one of the power supply of the transducers is
100 m (328 ft).
The controller incorporates a restorable thermal protection of the power supplies against the short circuit and the overload.
For the settings about the analog inputs look at chapter 6 “CONFIGURATION”.
PROG
Programming and debugging port.
POWER SUPPLY
Power supply.
Terminal
Meaning
V
≅
power supply controller (24 VAC / 20... 40 VDC)
V
≅