EVCO EPH4EXP Hardware manual User Manual
Page 48

EVCO S.p.A.
c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 48 of 116
DIGITAL OUTPUTS
In c-pro 3 EXP hecto+.
Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).
Terminal
Meaning
CO1/2
common digital outputs 1 and 2
NO1
normally open contact digital output 1
NO2
normally open contact digital output 2
NO3
normally open contact digital output 3
CO3/4/5
common digital outputs 3, 4 and 5
CO3/4/5
common digital outputs 3, 4 and 5
NO4
normally open contact digital output 4
NO5
normally open contact digital output 5
Digital output 6 (electromechanical relay).
Terminal
Meaning
CO6
common digital output 6
NO6
normally open contact digital output 6
NC6
normally closed contact digital output 6
The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
ANALOG OUTPUTS (in c-pro 3 EXP hecto only)
Analog outputs.
Terminal
Meaning
VDC
power supply driving analog output 1 (24 VDC, 50 mA max.)
AO1
analog output 1 (PWM signal)
GND
ground
AO2
analog output 2 (configurable via configuration parameter for 0-20 mA / 4-20 mA / 0-10 V signal)
AO3