EVCO EPH4EXP Hardware manual User Manual
Page 93

EVCO S.p.A.
c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 93 of 116
Parameters (1)
AI3
- - -
- - -
- - -
NTC
kind of probe analog input 3
PTC
= PTC probe
NTC
= NTC probe
0-20mA = 0-20 mA transducer
4-20mA = 4-20 mA transducer
0-5V
= 0-5 V ratiometric transducer
0-10V
= 0-10 V ratiometric transducer
PT1000 = Pt 1000 probe
Parameters (1)
AI Err Time
0
240
s
2
analog inputs time-out (after this time without
communication with an analog input, the
expansion signals the analog input error)
Parameters (1)
AO1
- - -
- - -
- - -
PWM
kind of signal analog input 1
PWM
= PWM (Pulse With Modulation)
Parameters (1)
AO2
- - -
- - -
- - -
0-10V
kind of signal analog input 2
0-20mA = 0-20 mA
4-20mA = 4-20 mA
0-10V
= 0-10 V
Parameters (1)
AO3
- - -
- - -
- - -
0-10V
kind of signal analog input 3
0-20mA = 0-20 mA
4-20mA = 4-20 mA
0-10V
= 0-10 V
Parameters (2)
[ press button
RIGHT to
show it ]
I/O Timeout
1
240
s
60
time-out of the CANbus communication for
the test of the remote values of the I / O
(after
this
time
without
CANbus
communication, the I / O of the expansion is
disabled)
Networks / CAN
Bus
MyNode
1
127
- - -
2
local (or of the expansion) CAN node
address
Networks / CAN
Bus
Master
- - -
- - -
- - -
YES
enabling the operation as master in a CAN
network
YES
= yes
Networks / CAN
Bus
Baud
- - -
- - -
- - -
20K
CANbus communication baud rate
20K
= 20,000 baud
50K
= 50,000 baud
125K
= 125,000 baud
500K
= 500,000 baud
Networks / CAN
Bus
NetworkNode
[ 1 ] 0
[ 32 ]
127
- - -
[ 1 ] 99
address of a remote (or of a device in the
network) CAN node; example for [ 1 ] 2:
[ 1 ]
= node
2
= node’s address