EVCO EPH4EXP Hardware manual User Manual
Page 82

EVCO S.p.A.
c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 82 of 116
Networks / CAN
Bus
MyNode
1
127
- - -
1
local (or of the controller) CAN node address
Networks / CAN
Bus
Master
- - -
- - -
- - -
YES
enabling the operation as master in a CAN
network
YES
= yes
Networks / CAN
Bus
Baud
- - -
- - -
- - -
20K
CANbus communication baud rate
20K
= 20,000 baud
50K
= 50,000 baud
125K
= 125,000 baud
500K
= 500,000 baud
Networks / CAN
Bus
Timeout
1
60
s
5
remote (or with a device in the network)
CANbus communication time-out (after this
time without CANbus communication with a
device, it is excluded by the network)
Networks / CAN
Bus
NetworkNode
[ 1 ] 0
[ 32 ]
127
- - -
[ 1 ] 99
address of a remote (or of a device in the
network) CAN node; example for [ 1 ] 2:
[ 1 ]
= node
2
= node’s address
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
TSEG1
0
63
- - -
31
reserved
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
TSEG2
1
7
- - -
7
reserved
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
SJW
0
3
- - -
0
reserved
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
BTR(1)
1
15
- - -
15
reserved