5 analog inputs configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers
-
7 optoisolated digital inputs at 24 VAC / DC
-
3 analog outputs of which 1 non optoisolated PWM output and 2 non optoisolated outputs configurable via configuration
parameter for 0-20 mA / 4-20 mA / 0-10 V signal
-
8 digital outputs (electromechanical relays) of which three 5 res. A @ 250 VAC SPST outputs, four 8 res. A @ 250 VAC SPST
outputs and one 8 res. A @ 250 VAC SPDT output
-
4 non optoisolated communication ports of which 1 CAN port with CANbus communication protocol, 1 RS-485 port with
Modbus slave communication protocol, 1 RS-485 port with Modbus master / slave communication protocol (configurable via
application software) and 1 programming and debugging port
-
1 non optoisolated communication port for gateway c-pro 3 plug-in (available in c-pro 3 NODE mega only).
Through the I / O expansion c-pro 3 EXP hecto or c-pro 3 EXP hecto+ it is possible to increase the number of inputs and outputs.
c-pro 3 mega+ is available in the following versions:
-
with 122 x 32 pixel single colour LCD graphic display (black with rearlighting through white LEDs) and with a 6 buttons (with
preset functions) keyboard made of silicone rubber integrated in the controller, hereinafter also called “built-in versions”
-
blind (can be used for example with an user interface such as Vgraph, Vtouch or Vroom), hereinafter also called “blind
versions”.
The controllers have got:
-
real time clock
-
alarm buzzer (not available in the blind versions)
-
8 analog inputs of which 3 configurable via configuration parameter for NTC / 0-20 mA / 4-20 mA transducers and 5
configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V ratiometric / 0-10 V
transducers
-
12 optoisolated digital inputs at 24 VAC / DC
-
5 analog outputs of which 1 non optoisolated PWM output, 2 non optoisolated outputs configurable via configuration
parameter for PWM / 0-10 V signal and 2 non optoisolated outputs configurable via configuration parameter for 0-20 mA /
4-20 mA / 0-10 V signal
-
10 digital outputs (electromechanical relays) of which five 5 res. A @ 250 VAC SPST outputs, four 8 res. A @ 250 VAC SPST
outputs and one 8 res. A @ 250 VAC SPDT output
-
5 non optoisolated communication ports of which 1 CAN port with CANbus communication protocol, 1 CAN port or MP-Bus
port (according to the model), 1 RS-485 port with Modbus slave communication protocol, 1 RS-485 port with Modbus master /
slave communication protocol (configurable via application software) and 1 programming and debugging port.
Through the I / O expansion c-pro 3 EXP hecto or c-pro 3 EXP hecto+ it is possible to increase the number of inputs and outputs.
c-pro 3 EXP hecto is available in blind version and can be used for example with a programmable controller such as c-pro 3 hecto,
c-pro 3 hecto+, c-pro 3 mega or c-pro 3 NODE mega.
The expansion has got:
-
3 analog inputs configurable via configuration parameter for PTC / NTC / Pt 1000 probes / 0-20 mA / 4-20 mA / 0-5 V
ratiometric / 0-10 V transducers
-
5 non optoisolated free of voltage digital inputs
-
3 analog outputs of which 1 non optoisolated PWM output and 2 non optoisolated outputs configurable via configuration
parameter for 0-20 mA / 4-20 mA / 0-10 V signal
-
6 digital outputs (electromechanical relays) of which five 5 res. A @ 250 VAC SPST outputs and one 8 res. A @ 250 VAC
SPDT output
-
2 non optoisolated communication ports of which 1 CAN port with CANbus communication protocol and 1 port to update the
firmware of the instrument.