EVCO EPH4EXP Hardware manual User Manual
Page 72

EVCO S.p.A.
c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 72 of 116
Networks / CAN
Bus
[ press button
RIGHT to
show it ]
BTR(1)
1
15
- - -
15
reserved
Networks / BMS
(4)
MAC ID
-1
127
- - -
-1
local (or of the controller) BACnet MS/TP
node address
-1
= not enabled
Networks / BMS
(4)
Baud Rate
- - -
- - -
- - -
19200
BACnet MS/TP communication baud rate
9600
= 9,600 baud
19200
= 19,200 baud
38400
= 28,000 baud
76800
= 76,800 baud
Networks / BMS
(4)
Max Master
0
127
- - -
127
maximum number of master in a BACnet
MS/TP network
Networks / BMS
(4)
Max InfoFram
1
127
- - -
3
maximum number of packages transmitted
as master before giving the token
Networks / BMS
(4)
Device ID
1
4194303
- - -
108
identity in a BACnet MS/TP multinetwork
Networks /
UART1 (1)
Address
1
247
- - -
1
local (or of the controller) Modbus node
address in a RS-485 network wired on the
first RS-485 port
Networks /
UART1 (1)
Baud Rate
- - -
- - -
- - -
9600
Modbus communication baud rate in a
RS-485 network wired on the first RS-485
port
1200
= 1,200 baud
2400
= 2,400 baud
4800
= 4,800 baud
9600
= 9,600 baud
19200
= 19,200 baud
28800
= 28,000 baud
38400
= 38,400 baud
57600
= 57,600 baud
Networks /
UART1 (1)
Parity
- - -
- - -
- - -
EVEN
Modbus communication parity in a RS-485
network wired on the first RS-485 port
NONE
= no parity
ODD
= odd
EVEN
= even