The maximum length of the connecting cables of the CAN port depends on the baud rate of the CANbus communication, as
follows:
-
1,000 m (3,280 ft) with baud rate 20,000 baud
-
500 m (1,640 ft) with baud rate 50,000 baud
-
250 m (820 ft) with baud rate 125,000 baud
-
50 m (164 ft) with baud rate 500,000 baud.
Connect the CAN port using a twisted pair.
For the settings about the CAN port look at chapter 6 “CONFIGURATION”.
DIGITAL OUTPUTS
In c-pro 3 EXP hecto.
Digital outputs 1, 2, 3, 4 and 5 (electromechanical relays).
Terminal
Meaning
CO1/2
common digital outputs 1 and 2
NO1
normally open contact digital output 1
NO2
normally open contact digital output 2
CO3
common digital output 3
NO3
normally open contact digital output 3
CO4/5
common digital outputs 4 and 5
NO4
normally open contact digital output 4
NO5
normally open contact digital output 5
Digital output 6 (electromechanical relay).
Terminal
Meaning
CO6
common digital output 6
NO6
normally open contact digital output 6
NC6
normally closed contact digital output 6
The maximum length of the connecting cables of the digital outputs is 100 m (328 ft).
The maximum current allowed on the loads is 10 A.