The maximum lengths of the connecting cables are the followings:
•
power supply controller: 30 m (98 ft)
•
analog inputs: 100 m (328 ft), but AI6, AI7 and AI8 of c-pro 3 mega+ (10 m, 32 ft)
•
power supply transducers: 10 m (32 ft)
•
digital inputs: 100 m (328 ft), but DI8, DI9, DI10, DI11 and DI12 of c-pro 3 mega+
(10 m, 32 ft)
•
PWM analog output: 1 m (3.280 ft)
•
0-20 mA / 4-20 mA / 0-10 V analog outputs: 30 m (98 ft), but AO4 and AO5 of
c-pro 3 mega+ (10 m, 32 ft)
•
digital outputs (electromechanical relays): 100 m (328 ft), but DO9 and DO10 of
c-pro 3 mega+ (10 m, 32 ft)
•
RS-485 ports: 1,000 m (3,280 ft); also look at the Manuale Modbus specifications
and implementation guides
•
MP-Bus port: 10 m (32 ft)
•
CAN ports:
-
1,000 m (3,280 ft) with baud rate 20,000 baud
-
500 m (1,640 ft) with baud rate 50,000 baud
-
250 m (820 ft) with baud rate 125,000 baud
-
50 m (164 ft) with baud rate 500,000 baud
•
power supply user interface: 30 m (98 ft).
One suggests using the
connecting
kit
CJAV15
(female extractable screw
terminal
blocks
pitch
5.0 mm, 0.196 in; to order
separately).
For c-pro 3 mega and for
c-pro 3 NODE mega one
suggests
using
the
connecting kit CJAV16, for
c-pro
3
mega+
one
suggests
using
the
connecting
kit
CJAV21
(female extractable screw
terminal
blocks
pitch
5.0 mm, 0.196 in; to order
separately).
One suggests using the
connecting
kit
CJAV15
(female extractable screw
terminal
blocks
pitch
5.0 mm, 0.196 in; to order
separately).
To program the controller one has to use the programming
kit EVIF20TUXI (TTL / USB isolated serial interface + TTL
cable 2.5 m, 8 ft long + USB cable 2 m, 6 ft long; to order
separately).
Working temperature:
from -10 to 55 °C (14 to 131 °F) for the built-in v ersions, from -20 to 55 °C (-4 to 131 °F) for
the blind versions.
Storage temperature:
from -30 to 70 °C (-22 to 158 °F).
Working humidity:
from 5 to 95% of relative humidity without condensate.
Pollution situation:
2.
Working altitude:
from 0 to 2,000 m (0 to 6591 ft).
Transport altitude:
from 0 to 3,048 m (0 to 10,000 ft).