EVCO EPH4EXP Hardware manual User Manual
Page 110

EVCO S.p.A.
c-pro 3 | Hardware manual ver. 3.2 | Codice 114CP3E324
page 110 of 116
5 optoisolated digital inputs
at 24 VAC / DC.
12 optoisolated digital inputs
at 24 VAC / DC.
5 optoisolated digital inputs
at 24 VAC / DC.
Non optoisolated free of voltage digital inputs
Power supply:
no power supply.
Input resistance:
≥
to 10K
Ω
.
Protection:
no protection.
Optoisolated digital inputs at 24 VAC / DC
Power supply:
24 VAC (±15%), 50 / 60 Hz (±3 Hz) or 24 VDC (+66% -16%).
Input resistance:
≥
to 10K
Ω
.
Protection:
no protection.
Displays:
c-pro 3 hecto and c-pro 3
hecto+
c-pro 3 mega, c-pro 3
mega+ and c-pro 3 NODE
mega
c-pro 3 EXP hecto and
c-pro 3 EXP hecto+
signalling LEDs.
122 x 32 pixel single colour
LCD graphic display (black
with
rearlighting
through
white LEDs; not available in
the
blind
versions),
signalling LEDs.
signalling LEDs.
Analog outputs:
c-pro 3 hecto and c-pro 3
hecto+
c-pro 3 mega and c-pro 3
NODE mega
c-pro 3 EXP hecto and
c-pro 3 EXP hecto+
3 outputs:
•
1 non optoisolated PWM output
•
2 non optoisolated outputs configurable via configuration parameter for 0-20 mA /
4-20 mA / 0-10 V signal.
Power supply driving the PWM analog output: 24 VDC, 50 mA max.
The PWM analog output is usable on condition that the device is powered in alternate
current and the phase powering the device is the same powering the user driven by the
output.
c-pro 3 mega+
5 outputs:
•
1 non optoisolated PWM output (analog output 1)
•
2 non optoisolated outputs configurable via configuration parameter for 0-20 mA /
4-20 mA / 0-10 V signal
•
2 non optoisolated outputs configurable via configuration parameter for PWM /
0-10 V signal.
Power supply driving the PWM analog output 1: 24 VDC, 50 mA max.
The PWM analog output 1 is usable on condition that the device is powered in alternate
current and the phase powering the device is the same powering the user driven by the
output.