EVCO EVCSR338J9 User Manual

Page 38

background image

EVCO S.p.A.

Vcolor 338 S | Installer manual ver. 1.2 | Code 144VC338SE124

page 38 of 50

t13 0 999

°C/°F

(2)

90

temperature above which steam reduction is activated (referring to

the temperature detected by the steam reduction probe); see also

t14

t14

1

99

°C/°F (2)

5

differential of t13

PARAM.

MIN.

MAX.

U.M.

DEF.

TEMPERATURE ALARMS

A0

1

99

°C/°F (2)

10

differential of A1

A1 0 999

°C/°F

(2)

0

temperature higher than that at which the maximum temperature

alarm is activated (referring to the temperature detected by the

environment probe); see also A0 and A3

A2

0

240

min

0

maximum temperature alarm delay

A3

0

2

- - -

0

maximum temperature alarm type

0 = no alarm

1 = absolute (i.e. A1)

2 = relative to the work set-point (i.e. “work set-point + A1”)

A4 0

80/175

°C/°F

(2)

70

temperature above which the temperature of use alarm is activated

(referring to the temperature of use of the control module)

0 = no alarm

PARAM.

MIN.

MAX.

U.M.

DEF.

DIGITAL INPUTS

i0

0

1

- - -

0

type of door micro switch input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i1

0

1

- - -

0

type of fan circuit breaker protection input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i2

0

1

- - -

0

fan circuit breaker protection input type

0 = for potential free contact (clamps 14 and 16)

1 = for high voltage contact (clamps 51 and 52)

i3

0

1

- - -

0

type of contact of the on/stand-by input

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)

i4

0

1

- - -

0

type of electric absorption input contact

0 = normally open (input active with closed contact)

1 = normally closed (input active with open contact)