EVCO EVCSR338J9 User Manual
Page 38

EVCO S.p.A.
Vcolor 338 S | Installer manual ver. 1.2 | Code 144VC338SE124
page 38 of 50
t13 0 999
°C/°F
(2)
90
temperature above which steam reduction is activated (referring to
the temperature detected by the steam reduction probe); see also
t14
t14
1
99
°C/°F (2)
5
differential of t13
PARAM.
MIN.
MAX.
U.M.
DEF.
TEMPERATURE ALARMS
A0
1
99
°C/°F (2)
10
differential of A1
A1 0 999
°C/°F
(2)
0
temperature higher than that at which the maximum temperature
alarm is activated (referring to the temperature detected by the
environment probe); see also A0 and A3
A2
0
240
min
0
maximum temperature alarm delay
A3
0
2
- - -
0
maximum temperature alarm type
0 = no alarm
1 = absolute (i.e. A1)
2 = relative to the work set-point (i.e. “work set-point + A1”)
A4 0
80/175
°C/°F
(2)
70
temperature above which the temperature of use alarm is activated
(referring to the temperature of use of the control module)
0 = no alarm
PARAM.
MIN.
MAX.
U.M.
DEF.
DIGITAL INPUTS
i0
0
1
- - -
0
type of door micro switch input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i1
0
1
- - -
0
type of fan circuit breaker protection input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i2
0
1
- - -
0
fan circuit breaker protection input type
0 = for potential free contact (clamps 14 and 16)
1 = for high voltage contact (clamps 51 and 52)
i3
0
1
- - -
0
type of contact of the on/stand-by input
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)
i4
0
1
- - -
0
type of electric absorption input contact
0 = normally open (input active with closed contact)
1 = normally closed (input active with open contact)