5commissioning 5.1 commissioning – EVCO EVCSR338J9 User Manual
Page 15

EVCO S.p.A.
Vcolor 338 S | Installer manual ver. 1.2 | Code 144VC338SE124
page 15 of 50
5
COMMISSIONING
5.1
Commissioning
Operate as indicated:
1.
Install the device using the methods illustrated in the 2 “DIMENSIONS AND INSTALLATION” chapter, following all warnings
given in the 2.5 “Installation warnings” paragraph.
2.
Connect the device electrically using the methods illustrated in the 3 “ELECTRIC CONNECTION” chapter, following all
warnings given in the 3.2 “Warnings for the electric connection” paragraph, without connecting the power supply and the
mains electricity.
3.
Connect the device power supply: a splash screen will be displayed for a few seconds.
4.
Set the time, the date and the day of the week; see paragraph 14.1 “Setting the time, date and day of the week”.
5.
Configure the device with the procedure illustrated in the paragraph 14.2 “Setting the configuration parameters”.
The following table illustrates the meaning of the configuration parameters; the parameters are listed with the order,
according to which, it is appropriate that the device is configured.
PARAM.
MEANING
FACTORY SETTING
P0
probe type
0 = thermocouple
J
1 = thermocouple
K
2 = Pt 100 2 wires
0
P1
unit of measurement
0 =
°C
1 =
°F
0
P2
enabling the needle probe
1 =
YES
0
F0
type of fan management
0 = in “on/off” mode and at single speed
1 = in “on/off” mode, with single speed and with inversion of the direction of
rotation of the fan
2 = in “on/off” mode, with dual speed and with inversion of the direction of
rotation of the fan
3 = in modulating mode and with inversion of the direction of rotation of the
fan
0
t0
steam generation mode
0 = direct
1 = with an external humidifier
2 = combined (i.e. direct and with external humidifier)
0
u0
type of vent output contact
0 = normally open (vent open with closed contact)
1 = normally closed (vent open with open contact)
0
u1
utility managed by the vent output
0 = ELECTROVALVE
ON/OFF
1 = MOTORISED
ELECTROVALVE - in this case the u2, u3 and u4 parameters
will assume significance
0