Table H-1. BMS II Standard Input Register Address Mapping-Cont.

Modbus Data

Address (Hex)

Menu Item

Units and Range

Comments

0x0027

Boiler 15 Status
(Net Boiler 15)

119 = Not On-Line
120 = On-Line But Not Fired
1–40 = Fired & Sequence
121 = On-Line But Disabled
122 = On-Line But Faulted

0x0028

Boiler 16 Status

(Net Boiler 16)

Same As Above

0x0029

Boiler 17 Status

(Net Boiler 17)

Same As Above

0x002A

Boiler 18 Status

(Net Boiler 18)

Same As Above

0x002B

Boiler 19 Status

(Net Boiler 19)

Same As Above

0x002C

Boiler 20 Status

(Net Boiler 20)

Same As Above

0x002D

Boiler 21 Status

(Net Boiler 21)

Same As Above

0x002E

Boiler 22 Status

(Net Boiler 22)

Same As Above

0x002F

Boiler 23 Status

(Net Boiler 23)

Same As Above

0x0030

Boiler 24 Status

(Net Boiler 24)

Same As Above

0x0031

Boiler 25 Status

(Net Boiler 25)

Same As Above

0x0032

Boiler 26 Status

(Net Boiler 26)

Same As Above

0x0033

Boiler 27 Status

(Net Boiler 27)

Same As Above

0x0034

Boiler 28 Status

(Net Boiler 28)

Same As Above

0x0035

Boiler 29 Status

(Net Boiler 29)

Same As Above

0x0036

Boiler 30 Status

(Net Boiler 30)

Same As Above