beautypg.com

Rs232 wiring at the bms ii, Installation, 9 rs232 wiring at the bms ii – AERCO BMS II BOILER User Manual

Page 29: Figure 2-12. sample network connections to ems

background image

INSTALLATION

2-17

2.9 RS232 WIRING AT THE BMS II

The BMS II communicates with an external Energy Management System (EMS) or Building Automation
System (BAS) utilizing the wiring terminals labeled RXD (Receive Data), TXD (Transmit Data) and 232
ISO GND
(Isolated Ground). If the EMS does not contain an RS232 port, a RS485-to-RS232 Converter
(AERCO Part No. 124943) is required to communicate with the BMS II. If a Converter is required, it can
be installed inside the wiring compartment of the BMS II, or installed externally. The BMS II provides an
isolated 12 VDC output terminal (ISO 12V) which can be used to power AERCO’s RS485-to-RS232
Converter if needed. Refer to Figure 2-12 for sample network layouts.

RS232

(50 FT. MAX.)

EMS

T+/R+

SHLD

RS

485

PORT

T-/R-

SEE NOTE 1

TO BOILERS

CONTROLLED

VIA RS485

NETWORK

(4000 FT. MAX.)

485

PORT

RXD

TXD

+(B)

-(A)

SHLD

BMS II

232

PORT

ISO

GND

+

-

TXD

RXD
GND

RS485-TO-RS232

CONVERTER

RS485

(4000 FT. MAX.)

ISO

12V

SEE

NOTE 2

T+

R-

R+

T-

SHIELD

4

-WIRE RS

485

PORT

DETAIL “A”

NOTES:

1. IF THE EMS CONTAINS A 4-WIRE RS485 PORT,
SEE DETAIL “A”.

2. THE BMS II PROVIDES A 12V OUTPUT IF
NEEDED TO POWER THE RS485-TO-RS232
CONVERTER.

RXD

TXD

+(B)

-(A)

SHLD

TO BOILERS

CONTROLLED

VIA RS485

NETWORK

(4000 FT. MAX.)

BMS II

485

PORT

RS232 (50 FT. MAX.)

EMS

TXD

GND

RS

232

PORT

RXD

232

PORT

ISO

GND

EMS WITH RS232 PORT

EMS WITH ONLY RS485 PORT

Figure 2-12. Sample Network Connections To EMS