Appendix h – AERCO BMS II BOILER User Manual
Page 103

APPENDIX H
H-11
APPENDIX H
(cont.)
__________________________
Table H-2. BMS II Standard Holding Register Address Mapping
Modbus Data
Address (Hex)
Menu Item
Units and Range
Default/Comments
0x005E
Net Boiler 3
Address
Address for Network Boiler 3 Default = 0
0x005F
Net Boiler 4
Address
Address for Network Boiler 4 Default = 0
0x0060
Net Boiler 5
Address
Address for Network Boiler 5 Default = 0
0x0061
Net Boiler 6
Address
Address for Network Boiler 6 Default = 0
0x0062
Net Boiler 7
Address
Address for Network Boiler 7 Default = 0
0x0063
Net Boiler 8
Address
Address for Network Boiler 8 Default = 0
0x0064
Net Boiler 9
Address
Address for Network Boiler 9 Default = 0
*0x0065
Net Boiler 10
Address
Address for Network Boiler
10
Default = 0
0x0066
Net Boiler
11address
Address for Network Boiler
11
Default = 0
0x0067
Net Boiler 12
Address
Address for Network Boiler
12
Default = 0
0x0068
Net Boiler 13
Address
Address for Network Boiler
13
Default = 0
**0x0069
Net Boiler 14
Address
Address for Network Boiler
14
Default = 0
0x006A
Net Boiler 15
Address
Address for Network Boiler
15
Default = 0
0x006B
Net Boiler 16
Address
Address for Network Boiler
16
Default = 0
0x006C
Net Boiler 17
Address
Address for Network Boiler
17
Default = 0
0x006D
Net Boiler 18
Address
Address for Network Boiler
18
Default = 0
0x006E
Net Boiler 19
Address
Address for Network Boiler
19
Default = 0
0x006F
Net Boiler 20
Address
Address for Network Boiler
20
Default = 0