Appendix h – AERCO BMS II BOILER User Manual
Page 101

APPENDIX H
H-9
APPENDIX H
(cont.)
__________________________
Table H-2. BMS II Standard Holding Register Address Mapping
Modbus Data
Address (Hex)
Menu Item
Units and Range
Default/Comments
0x0034
Offset On Time
Day 1 – Hours
00 to 23 Hours
Default = 0
0x0035
Offset On Time
Day 2 – Hours
00 to 23 Hours
Default = 0
0x0036
Offset On Time
Day 3 – Hours
00 to 23 Hours
Default = 0
0x0037
Offset On Time
Day 4 – Hours
00 to 23 Hours
Default = 0
0x0038
Offset On Time
Day 5 – Hours
00 to 23 Hours
Default = 0
0x0039
Offset On Time
Day 6 – Hours
00 to 23 Hours
Default = 0
0x003A
Offset On Time
Day 7 – Hours
00 to 23 Hours
Default = 0
0x003B
Offset Enable
0 or 1
0 = Disabled
1 = Enabled
Default = 0
(Disabled)
0x003C
Header Temp Offset -10 to 10°F
Default = 0°F
0x003D
System Start
Interlock
1, 2 or 3
1 = Intlk1 Opens Start Relay
2 = Intlk2 Opens Start Relay
3 = Either Intlk Opens Start
Relay
Default = 1
(Intlk 1)
0x003E Thru
0x0045
(Reserved)
0x0046
Offset Off Time
Sun. – Minutes
0 to 59 Minutes
Default = 0
0x0047
Offset Off Time
Mon. – Minutes
0 to 59 Minutes
Default = 0
0x0048
Offset Off Time
Tue.– Minutes
0 to 59 Minutes
Default = 0
0x0049
Offset Off Time
Wed.– Minutes
0 to 59 Minutes
Default = 0
0x004A
Offset Off Time
Thu – Minutes
0 to 59 Minutes
Default = 0
0x004B
Offset Off Time
Fri. – Minutes
0 to 59 Minutes
Default = 0