APPENDIX G

G-2

APPENDIX G

(cont.)

__________________________




Programming Procedure

BMS II functions which can be viewed or changed are listed in Table J-1 along with their
corresponding command numbers. Functions which can only be viewed (such as actual sensor
readings) are marked “Read Only”. Viewing or changing function values is accomplished as
follows:

1. Select the number of the desired command from Table J-1.

2. To view a parameter, type ?, followed by the command number and then press return (). For

example, to view command no. 00 (HEADER TEMPERATURE), enter:

?00


The header temperature reading will be displayed. All temperature readings are in °F.

3. To program (set) a BMS parameter, type @, followed by the command number, an equal sign, the

parameter value and a trailing zero. For example, to set command 05 (SYSTEM OUTSIDE AIR
START TEMPERATURE) to 65°F, enter:


@05=650

Use the above steps to view and/or program the desired BMS II functions listed in Table G-1.