Appendix b, Status and fault messages – AERCO BMS II BOILER User Manual

Page 71

background image

APPENDIX B

B-1

APPENDIX B

_____________________________

STATUS AND FAULT MESSAGES

DISPLAY MESSAGES

DESCRIPTION

STATUS MESSAGES:

FAIL SAFE MODE
ACTIVATED

The system is running in the Constant Setpt mode due to loss of the
Remote signal or Outdoor Air sensor input.

NETWORK DISABLED
MODBUS LISTEN

“Forced Listen Only Mode” has been activated. All Modbus commands
except “restart Communications Options” will be ignored. The BMS II will
operate in the Fail Safe Mode.

OUTSIDE AIR TEMP
NOT CONNECTED

The Outdoor Air Temperature Sensor is not installed and connected.

RETURN TEMP
NOT INSTALLED

The Boiler Return Temperature Sensor is not installed.

FAULT MESSAGES

OUTDOOR SENSOR
ERROR

The Outdoor Air Temperature Sensor signal is out of range.

HEADER SENSOR
ERROR

The Header Temperature Sensor signal is out of range or disconnected.

RETURN SENSOR
ERROR

The Return Temperature Sensor signal is out of range.

INTERLOCK 1
ERROR

Interlock 1 input is open.

INTERLOCK 2
ERROR

Interlock 2 input is open.

4 – 20 mA INPUT
ERROR

The 4 – 20 mA Remote Input signal is lost.

MODBUS TIMEOUT
ERROR

The Modbus remote input information was not received within the
network timeout period.