Appendix g, Table g-1. bms ii commands – AERCO BMS II BOILER User Manual
Page 88

APPENDIX G
G-4
APPENDIX G
(cont.)
__________________________
Table G-1. BMS II COMMANDS
No.
COMMAND
ENTRY RANGE
FACTORY
DEFAULT
26
Not Used
27
28
29
Reserved
30
Maximum Power Input
50 to 100
100
31
System Interlock Configuration
0 = Always Enabled
1 = Start Enabled
1 = Start Enabled
32
Real Time Clock - Minutes
00 to 59
Present Time
33
Real Time Clock - Hours
00 to 23
Present Time
34
Real Time Clock - Day Of Week
1 to 7
Present Day
35
Real Time Clock - Year
00 to 99
Present Year
36
Real Time Clock - Day Of Month
00 to 31
Present Day
37
Real Time Clock - Month
00 to 12
Present Month
38
(Day 1 – Sun.)
Thru
Offset Temperatures (Day 1-7)
-50 to +50°F
All Set To 0°F
44
(Day 7 – Sat.)
45
(Sun.)
Thru Offset ON Time – Minutes (Sun.-Sat.)
00 to 59
All Set to Zero
51
(Sat.)
52
(Sun.)
Thru
Offset ON Time – Hours (Sun.-Sat.)
00 to 23
All Set To Zero
58
(Sat.)
59
Offset Enable
0 = Disabled
1 = Enabled
0 = Disabled
60
Header Temp Offset (°F)
-10°F to 10°F
0
61
System Start Interlock
1 = Intlk 1 Opens
Start Relay
2 = Intlk 2 Opens Start
Relay
3 = Either Intlk Opens
Start Relay
1 = Intlk 1
70
(Sun.)
Thru Offset OFF Time – Minutes (Sun.-Sat.)
00 to 59
All Set To Zero
76
Sat.)
77
(Day 1)
Thru Offset OFF Time – Hours (Day 1-7)
0 to 23
All Set To Zero
83
(Day 7)
84
(Reserved)
85
Not Used
0 or 1