Appendix g, Table g-1. bms commands – (continued) – AERCO BMS II BOILER User Manual
Page 89

APPENDIX G
G-5
APPENDIX G
(cont.)
__________________________
Table G-1. BMS COMMANDS – (Continued)
No.
COMMAND
ENTRY RANGE
FACTORY
DEFAULT
86
Remote Signal
0 or 1
0 = 4 - 20 mA
1 = Modbus
0 = 4 - 20 mA
87
RS232 Mode
0 or 1
0 = Normal
1 = Modbus
1 = Modbus
88
RS232 Baud Rate
0=2400, 1=4800,
2=9600, 3=14400,
4=19200
2 = 9600
89
Number Of Network Boilers
0 to 32
2
90
Min Slave Address
0 to 127
0
91
Max Slave Address
0 to 127
0
92
Net Boiler 1 Address
Address for Network
Boiler 1
001
93
Net Boiler 2 Address
Address for Network
Boiler 2
002
94
Net Boiler 3 Address
Address for Network
Boiler 3
000
95
Net Boiler 4 Address
Address for Network
Boiler 4
000
96
Net Boiler 5 Address
Address for Network
Boiler 5
000
97
Net Boiler 6 Address
Address for Network
Boiler 6
000
98
Net Boiler 7 Address
Address for Network
Boiler 7
000
99
Net Boiler 8 Address
Address for Network
Boiler 8
000
100
Net Boiler 9 Address
Address for Network
Boiler 9
000
101
Net Boiler 10 Address
Address for Network
Boiler 10
000
102
Net Boiler 11 Address
Address for Network
Boiler 11
000
103
Net Boiler 12 Address
Address for Network
Boiler 12
000
104
Net Boiler 13 Address
Address for Network
Boiler 13
000
105
Net Boiler 14 Address
Address for Network
Boiler 14
000
106
Net Boiler 15 Address
Address for Network
Boiler 15
000