APPENDIX G

G-7

APPENDIX G

(cont.)

__________________________


Table G-1. BMS II COMMANDS – (Continued)

No.

COMMAND

ENTRY RANGE

FACTORY DEFAULT

129

Modbus Pass-Thru

0 = Disabled
1 = Enabled

0 = Disabled

130

Header Temp Deadband

01 to 15°F

05°F

131

Outside Temp Sensor Offset

-10.0°F to 10.0°F

0.0°F

132

Ramp Up %/Min

000 to 300

20

133

Ramp Down %/Min

000 to 300

200

134

Fault Alarm Boilers

No Blr Faults
All Blr faults

No Blr Faults

135

4-20 mA Offset

-1.00 to 1.00 mA

0.0 mA

136

Return Sensor Offset

-10.0 to 10.0°F

0.0°F

137

Load Start Pct

000 to 100

1

138 Load Stop Pct

000 to 100

0

150

I/O Status

00 to 255

Bit 0 = AUX Relay
Bit 1 = Fault Relay
Bit 2 = Sys Start Relay
Bit 3 = Empty
Bit 4 = Setback
Bit 5 = Interlock 2
Bit 6 = Interlock 1
Bit 7 = Empty

151

&

Up

(Reserved For Future Expansion)

Undefined