Appendix a, Bms ii menus – AERCO BMS II BOILER User Manual

Page 70

background image

APPENDIX A

A-4

APPENDIX A

_____________________________

BMS II MENUS

- Continued

AVAILABLE CHOICES OR LIMITS

MENU LEVEL & OPTION

MINIMUM

MAXIMUM

DEFAULT

RELAY MENU

SYS START TEMP

032°F

120°F

070°F

SYS START OPTION

TEMP ONLY,

TEMP AND LOAD

TEMP ONLY

SYS START INTLK

DISABLED

INTERLOCK 1
INTERLOCK 2

INTERELOCK 1&2

INTERLOCK 1

AUX RELAY OPEN

000%

099%

045%

AUX RELAY CLOSE

100% FIRE RATE,

100% AND OFF

100% AND OFF

FAULT ALRM RELAY

ALL FAULTS,

NO INTERLOCK,

INTERLOCK 2,

INTERLOCK 1

ALL FAULTS

FAULT ALARM BLRS

NO BLR FAULTS,
ALL BLR FAULTS

NO BLR FAULTS

FAULT ALRM CLEAR

AUTOMATIC,

MANUAL RESET

AUTOMATIC

CALIBRATION MENU

HDR SENS OFFSET

-10.0°

10.0°

00.0°

OUTD SENS OFFSET

-10.0°

10.0°

00.0°

4 – 20 MA OFFSET

-10.0

10.0

00.0

RET SENS OFFSET

-10.0°

10.0°

00.0

RAMP UP %/MIN

000

300

020

RAMP DOWN %/MIN

000

300

200

LOAD START PCT

000

100

1

LOAD STOP PCT

000

100

0

RESET DEFAULTS

NO,

YES (DONE If Selected)

NO