APPENDIX H

H-12

APPENDIX H

(cont.)

__________________________


Table H-2. BMS II Standard Holding Register Address Mapping

Modbus Data

Address (Hex)

Menu Item

Units and Range

Default/Comments

0x0070

Net Boiler 21
Address

Address for Network Boiler
21

Default = 0

0x0071

Net Boiler 22
Address

Address for Network Boiler
22

Default = 0

0x0072

Net Boiler 23
Address

Address for Network Boiler
23

Default = 0

0x0073

Net Boiler 24
Address

Address for Network Boiler
24

Default = 0

0x0074

Net Boiler 25
Address

Address for Network Boiler
25

Default = 0

0x0075

Net Boiler 26
Address

Address for Network Boiler
26

Default = 0

0x0076

Net Boiler 27
Address

Address for Network Boiler
27

Default = 0

0x0077

Net Boiler 28
Address

Address for Network Boiler
28

Default = 0

0x0078

Net Boiler 29
Address

Address for Network Boiler
29

Default = 0

0x0079

Net Boiler 30
Address

Address for Network Boiler
30

Default = 0

0x007A

Net Boiler 31
Address

Address for Network Boiler
31

Default = 0

**0x007B

Net Boiler 32
Address

Address for Network Boiler
32

Default = 0

0x007C

Network Baud

0=2400, 1=4800, 2=9600,
3=14400, 4=19200

2 = 9600

0x007D

Network Timeout

5 to 240 sec

Default = 60 sec.

0x007E

Password Lo

0 to 255 (73)

Default = 0

0x007F

Password Hi

0 to 255 (79)

Default = 0

0x0080

Modbus Control
Type

0 = Round-Robin
1 = Broadcast

Default = 0
(Round Robin)

0x0081

Modbus Pass-Thru

0 = Disabled
1 = Enabled

Default = 0 (Disabled)

0x0082

Header Dead Band

1 to 15°F

Default = 5°F